What do Navien error codes mean? NPE-2 tankless code table

Last reviewed Expert review pending 4 min read 4 sources

Short answer

Navien codes start with E. E003 means the burner did not light, E012 is flame loss, E016 and E030 are overheating often tied to a clogged inlet filter or scale, E110 is blocked venting, and E760 means a flush is due. Owners can check gas, power, filters and vents. Sensor and board codes need a pro.

Key facts

  • Navien's NPE-2 manual lists E407 as the hot water outlet sensor fault and E515 as a main circuit board fault.[1]
  • Navien's manual ties E016 (heat exchanger overheating) to a clogged cold water inlet filter or scale, both owner-level checks to start.[1]
  • Navien technical support is listed in the NPE-2 manual at 1-800-519-8794.[1]

Before you use this table

If you smell gas, do not reset anything. Leave on foot, avoid anything that can spark, and call the gas utility and 911 from a safe place[3].

This table covers the Navien NPE-2 condensing tankless line (NPE-180A2, 210A2 and 240A2, and the matching S2 models). The meanings are our paraphrase of the NPE-2 user's manual, not Navien's text[1]. For other Navien models, use the manual on Navien's downloads page[2].

"Power cycle once" means turning the unit off and back on one time. If the code returns, stop.

CodeWhat it meansSafe homeowner checkCall a pro when
E003Ignition failure: the burner did not lightMain gas valve to the unit open; other gas appliances work; propane not emptyStill no light: gas pressure, igniter or flame rod
E004False flame: flame sensed when there should be noneUnit plugged into a properly grounded outletIt returns: flame rod or board diagnosis
E012Flame lost after lightingClean the intake air filter per the manual; check the grounded outletIt returns: gas supply or vent diagnosis
E016Heat exchanger overheatingClean the cold water inlet filter; schedule a flushIt returns after both: descaling or sensor checks
E030Exhaust too hot; the unit shuts down above about 149 F flue temperatureClean the inlet filter; schedule a flushIt returns: exhaust sensor and vent checks
E031Burner overheatingNoneAlways
E046High-limit safety tripped or abnormalNoneAlways
E047Exhaust temperature sensor open or shortedNoneAlways: sensor replacement
E060Dual venturi faultNoneAlways
E109Fan motor faultClean the intake air filterIt returns: fan replacement
E110Abnormal air pressure: blocked exhaust or intakeClear snow, nests or debris from the outside terminals; clean the intake filterIt returns: vent repair
E407Hot water outlet temperature sensor open or shortedNoneAlways: sensor replacement
E421, E432, E441Other water temperature sensors open or shorted (cold inlet 1, cold inlet 2, hot water inlet 2)NoneAlways
E434Water flow adjustment valve faultNoneAlways
E438Circulation pump fault (pump or air handler setups)Note whether the pump hums or vibrates, and tell the proAlways
E439Flow sensor faultNoneAlways
E445Bypass mixing valve faultNoneAlways
E515Main circuit board faultConfirm a grounded outlet; power cycle onceIt returns: board replacement
E517DIP switch setting errorNoneAlways: installer settings need correcting
E593, E594, E615Front panel key, memory or input faultsPower cycle onceIt returns
E736Cascade (multi-unit) communication faultNoneAlways
E740Outdoor temperature sensor fault (air handler setups)NoneAlways
E760Flushing or service reminderBook a flush or routine servicen/a
E762Vent pipe not seated properly at the unitTurn the unit off; do not run itAlways: a loose vent can leak exhaust
E773, E788Gas type mismatch: the unit or its settings do not match the gas suppliedNoneAlways: gas settings are licensed gas work
E782Main panel communication faultNoneAlways
E785Flow switch or sensor fault (air handler setups)NoneAlways

Source: Navien NPE-2 User's Information Manual[1], paraphrased.

Myth: E515 is the outlet sensor

You will find websites that list E515 as the hot water outlet sensor. Navien's NPE-2 manual says otherwise: E407 is the outlet sensor, and E515 is the main circuit board[1]. A sensor and a board are very different parts and prices, so check the manual for your exact model before anyone orders parts.

The two filters that clear many Navien codes

Navien units have two owner-serviceable filters, and dirty ones show up behind several codes[1]:

  • Cold water inlet filter. A clogged one restricts flow and can cause overheating codes (E016, E030).
  • Intake air filter. A dirty one can cause flame loss and fan faults (E012, E109, E110).

The owner's manual shows how to reach and clean both. If either code returns after cleaning, call a pro.

Hard water and E760

E760 is a reminder, not a failure. Scale builds inside the heat exchanger over time, especially in hard water, and leads to overheating codes if it is ignored. HomeGuide's 2025 range for a tankless flush and descale is $75 to $300[4].

When to call a pro

  • E762 (vent not seated) or E773 and E788 (gas type mismatch): turn the unit off.
  • Any overheat code that returns after cleaning the inlet filter.
  • Any sensor, valve, pump, fan or board code.
  • E003 or E012 that returns with gas confirmed on.

More questions

What is the difference between Navien A2 and S2 models?

NPE-A2 models have a built-in buffer tank and recirculation pump; NPE-S2 models do not. Pump codes such as E438 mainly apply to A2 units or installs with an external recirculation pump.

Do Navien combi boilers use the same codes?

The NCB combi boilers share many codes for common parts like ignition, flame, sensors and fans, but add space-heating codes such as low system pressure. Use the NCB manual for those.

Sources

  1. NPE-2 User's Information Manual (EN, 2020-12 revision), Navien. Accessed 2026-10-06.